Victron MultiPlus-II GX – 48 V, 6,000 W, 100 A (PMP482606000)

Victron Energy · inverter_charger

Technische Daten (aus Herstellerdokumenten)

FeldWertBedingungQuelle
aCConnectionTerminalType Screw terminals 13 mm² (6 AWG) - victron_api_2026_11
aCInputFrequencyRange [45, 65] Hz - victron_api_2026_11
aCInputVoltageRange [187, 265] VAC - victron_api_2026_11
aCInputVoltageRange1 [187, 265] VAC - victron_api_2026_11
aCOutputFrequency 50 Hz - victron_api_2026_11
aCOutputVoltage 230 VAC - victron_api_2026_11
AuxiliaryOutput ja - victron_api_2026_11
batteryConnectionTerminalType M8 bolts - victron_api_2026_11
batteryVoltageNominal 48 V - victron_api_2026_11
chargeAlgorithm Adaptive, 4-stage - victron_api_2026_11
chargeVoltageAbsorption 57.6 VDC - victron_api_2026_11
chargeVoltageFloat 55.2 VDC - victron_api_2026_11
chargeVoltageStorage 52.8 VDC - victron_api_2026_11
communicationPort VE.Bus - victron_api_2026_11
communicationPortGeneral ja - victron_api_2026_11
computerProgramming ja - victron_api_2026_11
continuous_output_power 6000 W aus Victron-Feld contPowerW25 (bei 25 °C) victron_api_2026_11
contPowerW25 6,000 W - victron_api_2026_11
contPowerW40 5,700 W - victron_api_2026_11
contPowerW65 4,600 W - victron_api_2026_11
dCInputVoltageRange [38, 60] VDC Batteriespannung am DC-Eingang, nicht die PV-Spannung victron_api_2026_11
depth 150 mm - victron_api_2026_11
externalAcCurrentSensor 50A or 100A (optional) - victron_api_2026_11
fanAssistCooling ja - victron_api_2026_11
height 644 mm - victron_api_2026_11
maxAcInputCurrent 50 A - victron_api_2026_11
maxAltitude 2,000 m - victron_api_2026_11
maxAppFeedinPower 6,000 W - victron_api_2026_11
maxEfficiency 96 % - victron_api_2026_11
maxHumidity 95 % - victron_api_2026_11
maximumBatteryChargeCurrent 100 A - victron_api_2026_11
max_charge_current 100 A aus Victron-Feld maximumBatteryChargeCurrent victron_api_2026_11
numberAcInputs 1 - victron_api_2026_11
operatingTempRange [-40, 65] °C - victron_api_2026_11
parallelOperation ja - victron_api_2026_11
peakPowerRating 11,000 W - victron_api_2026_11
powerAssist ja - victron_api_2026_11
powerControl ja - victron_api_2026_11
programmableRelay AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC - victron_api_2026_11
protectionCategory IP21 - victron_api_2026_11
protections Output short-circuit,Overload,High battery voltage,Low battery voltage,Over temperature,AC voltage on inverter output,Excessive DC ripple - victron_api_2026_11
relayTerminal Screw terminal 3-pole - victron_api_2026_11
remoteTerminal On / Off - victron_api_2026_11
remoteTerminalType Screw terminal two pole - victron_api_2026_11
ShortName 6k5 - victron_api_2026_11
temperatureSensor Included - victron_api_2026_11
threePhaseOperation ja - victron_api_2026_11
transferSwitchCurrentRating 50 A - victron_api_2026_11
vebusTerminalType Two RJ45 terminals - victron_api_2026_11
weight 29 kg - victron_api_2026_11
width 320 mm - victron_api_2026_11
zeroLoadPower 28 W - victron_api_2026_11
zeroLoadPowerAES 18 W - victron_api_2026_11
zeroLoadPowerSearch 8 W - victron_api_2026_11
Frage zur Victron MultiPlus-II GX – 48 V, 6,000 W, 100 A (PMP482606000) stellen