Technische Daten (aus Herstellerdokumenten)
| Feld | Wert | Bedingung | Quelle |
|---|---|---|---|
| aCConnectionTerminalType | M6 bolts | - | victron_api_2026_11 |
| aCInputFrequencyRange | [55, 65] Hz | - | victron_api_2026_11 |
| aCInputVoltageRange2 | [90, 140] V | - | victron_api_2026_11 |
| aCOutputFrequency | 60 Hz | - | victron_api_2026_11 |
| aCOutputVoltage | 120 VAC | - | victron_api_2026_11 |
| antiIslandingStandard | See our website | - | victron_api_2026_11 |
| AuxiliaryOutput | ja | - | victron_api_2026_11 |
| batteryConnectionTerminalType | M8 bolts (two for positive and two for negative connection) | - | victron_api_2026_11 |
| batteryVoltageNominal | 48 V | - | victron_api_2026_11 |
| chargeAlgorithm | Adaptive, 4-stage | - | victron_api_2026_11 |
| chargeVoltageAbsorption | 57.6 VDC | - | victron_api_2026_11 |
| chargeVoltageFloat | 55.2 VDC | - | victron_api_2026_11 |
| chargeVoltageStorage | 52.8 VDC | - | victron_api_2026_11 |
| communicationPort | VE.Bus | - | victron_api_2026_11 |
| communicationPortGeneral | ja | - | victron_api_2026_11 |
| continuous_output_power | 8000 W | aus Victron-Feld contPowerW25 (bei 25 °C) | victron_api_2026_11 |
| contPowerVA25 | 10,000 VA | - | victron_api_2026_11 |
| contPowerW25 | 8,000 W | - | victron_api_2026_11 |
| contPowerW40 | 6,500 W | - | victron_api_2026_11 |
| contPowerW65 | 4,500 W | - | victron_api_2026_11 |
| dCInputVoltageRange | [38, 66] VDC | Batteriespannung am DC-Eingang, nicht die PV-Spannung | victron_api_2026_11 |
| depth | 344 mm | - | victron_api_2026_11 |
| fanAssistCooling | ja | - | victron_api_2026_11 |
| frequencySelect | 60Hz | - | victron_api_2026_11 |
| height | 572 mm | - | victron_api_2026_11 |
| integratedTransferSwitch | ja | - | victron_api_2026_11 |
| maxEfficiency | 96 % | - | victron_api_2026_11 |
| maxFeedTroughCurrent | 2x 100A | - | victron_api_2026_11 |
| maxHumidity | 95 % | - | victron_api_2026_11 |
| maximumBatteryChargeCurrent | 140 A | - | victron_api_2026_11 |
| max_charge_current | 140 A | aus Victron-Feld maximumBatteryChargeCurrent | victron_api_2026_11 |
| numberAcInputs | 2 | - | victron_api_2026_11 |
| numberAcOutputs | 2 | - | victron_api_2026_11 |
| operatingTempRange | [-40, 65] °C | - | victron_api_2026_11 |
| ovciiiIcw | nein | - | victron_api_2026_11 |
| parallelOperation | ja | - | victron_api_2026_11 |
| peakPowerRating | 20,000 W | - | victron_api_2026_11 |
| pollutionDegree | 2 | - | victron_api_2026_11 |
| powerAssist | ja | - | victron_api_2026_11 |
| powerControl | ja | - | victron_api_2026_11 |
| programmableRelay | AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC | - | victron_api_2026_11 |
| protectionCategory | IP21 | - | victron_api_2026_11 |
| protections | Output short-circuit,Overload,High battery voltage,Low battery voltage,Over temperature,AC voltage on inverter output,Excessive DC ripple | - | victron_api_2026_11 |
| relayTerminal | Screw terminal 3-pole | - | victron_api_2026_11 |
| remoteTerminal | On / Off / Charger only | - | victron_api_2026_11 |
| remoteTerminalType | Screw terminal two pole | - | victron_api_2026_11 |
| temperatureSensor | Included | - | victron_api_2026_11 |
| threePhaseOperation | ja | - | victron_api_2026_11 |
| vebusTerminalType | Two RJ45 terminals | - | victron_api_2026_11 |
| weight | 58 kg | - | victron_api_2026_11 |
| width | 488 mm | - | victron_api_2026_11 |
| zeroLoadPower | 60 W | - | victron_api_2026_11 |
| zeroLoadPowerAES | 40 W | - | victron_api_2026_11 |
| zeroLoadPowerSearch | 15 W | - | victron_api_2026_11 |
Gerätebeziehungen
Cerbo GX (Baureihe, Praxis- und Kombinationswissen)
(Victron Energy)
Typ: kommunikation · Schnittstelle: VE.Bus (RJ45, Standard-UTP-Kabel) · Status: freigegeben
Einschränkung: Nur ein VE.Bus-System pro GX-Gerät; freie VE.Bus-Buchsen offen lassen